400A 16 Way 125A Outgoers Glazed.
- Comprises of IP3XD enclosure, pan assembly, neutral bar and earth bar
- Conforms to BS EN 61439-2. I nA = 400A, Inc = 125A, Icc = 50kA.
- Supplied without incoming kit, one of the incomer kits listed below must be used.
- Form 3B type 2 using outgoing terminal shield (form 3A without terminal shield).
- Removable gland plates are provided top and bottom for ease of installation
- Glazed door
Mounting method : | Surface mounted |
Colour : | Other |
Width : | 900mm |
Height : | 1550mm |
Depth : | 220mm |
Type of covering : | Cover |
EMC-version : | No |
Housing material : | Steel |
Type of closure : | Cylinder |
Degree of protection (IP rating) : | IP30 |
Transparent cover/door : | Yes |
With lock : | Yes |